Pressure transmitter selection in 7 steps
Step 1 — Measurement type
Gauge, absolute or differential. For level in a closed tank use a differential transmitter with the appropriate high/low side configuration.
Step 2 — Upper range limit (URL) from maximum working pressure
Choose a sensor range that covers the maximum working pressure with margin. Do not size URL from normal pressure alone.
Step 3 — Turndown and minimum span
Minimum usable span equals URL divided by turndown. Setting span far below URL amplifies error effects and may reach migration limits.
Step 4 — Total error, not headline accuracy
Reference accuracy is under reference conditions. Add ambient temperature effect, static pressure effect, long-term stability and installation error to get total error for your loop.
Step 5 — Wetted materials and process connection
Match diaphragm and fill fluid to the medium's chemistry and temperature. Confirm the process connection and, for DP, the manifold arrangement.
Step 6 — Protocol and approvals
HART for existing 4–20 mA loops; FF / PROFIBUS PA for new bus projects, subject to segment power and barriers. For hazardous areas determine zone, gas group and temperature class; for safety loops verify IEC 61508 product certification and IEC 61511 SIF design.
Step 7 — Calibration and maintenance
Define the calibration procedure and interval based on regulation, service severity and the loop error budget. Installation and calibration notes →